KYCM2WF series intelligent miniature circuit breakers have the characteristics of advanced and reasonable structure, reliable performance, high breaking capacity, and beautiful appearance. The shell material is composed of high-quality impact-resistant and high-flame retardant materials. It is suitable for indoor, AC 50Hz, rated voltage 230V, three-phase 400V, and rated current not exceeding 100A. It is mainly used for low-voltage terminal power distribution in industrial, commercial, civil buildings and infrastructure in buildings and similar places. Leakage, overload, short circuit, over-under-voltage, over-heating, and lack of equal protection can also be used for infrequent on-off operations. The leakage circuit breaker with the rated residual operating current less than 30mA can provide protection for personal electric shock.
Number of poles | 1P, 2P, 3P, 4P |
Breaking capacity | 1A-63A, 10kA |
80-100A, 6kA | |
Rated voltage | 230/400V AC |
Rated current | 1A-100A |
Residual current type | A type, AC type |
Residual current specifications | 30, 100, 300mA or adjustable |
Trip time | Standard type, time delay type, adjustable type |
Configurable leakage function | Shut down, alarm, alarm and protection |
Leakage self-test | Automatic non-trip self-check, remote and local trip self-check |
Short circuit protection | Type B, Type C, Type D |
Trip time | <0.1s |
Overcurrent protection | Thermal element + electronic |
Thermal trip | Inverse time limit |
Electronic trip | Inverse time or definite time |
Working current | Electronically adjustable |
Overvoltage protection | JB/T 12762 OUPA standard |
Overvoltage setting value | 275V |
Undervoltage setting value | 0.7Ue |
Action time | Standards compliant |
Meet the standard | Shut down, alarm, alarm and protection |
Terminal temperature rise protection | Alarm + protection |
Temperature rise alarm setting value | >50K |
Temperature rise action setting value | >60K |
Action time | 15min |
Temperature rise protection function can be configured | Shut down, alarm, alarm and protection |
Three-phase unbalance | Monitoring + alarm |
Lack of phase | Monitoring + alarm + protection |
Configurable function | Shut down, alarm, alarm and protection |